SIR-A
Overhead Control / Feeder Protection

Description

The Fanox SIR-A offers a complete Overhead Control / RTU and Feeder Protection solution with current, voltage, and frequency functions.
It is available with an auxiliary power supply of 24-230 Vdc / ac, 48-230 Vdc / ca, or 24-48 Vdc (depending on the model that best suits the installation).

SIR-A has 4 current channels and up to 6 voltage channels, with the advantage of measuring the voltage through capacitive and resistive sensors.

Adaptation C: has Thirteen (13) programmable alarm LEDs + 8 configurable keys with their associated configurable LED

Like all Fanox relays, SIR-A is intuitive for easy handling use and has flexible communication options; relays are provided with a local micro-USB front port and with remote communication with different options (ports and protocols) on the rear side:

  • Rear Serial Port: IEC60870-5-103, Modbus RTU or DNP3.0 Serial (selectable by general settings).
    • Adaptation B: Rear RS485 port
    • Adaptation C: Rear RS485 or RS232 port (selectable by the user, both ports are not available simultaneously)
  • Rear RJ45 Port: Modbus TCP/IP, DNP3.0 TCP/IP, IEC60870-5-104 (selectable by general settings) + SNTP Protocol + Web Server.
  • Rear RJ45: IEC61850

In case a CB is manually closed, a switch on to an existing fault may occur. This fault condition is critical if the overcurrent protection function does not clear the fault until the adjusted time delay is finished. It is necessary, in those cases, to clear the fault quickly using the SOTF function.

Data Sheet

    Get in touch with our Technical Support:

    Select your Country*

    The SIR-A is an Overhead Control / RTU & and Feeder Protection relay with current, voltage, and frequency functions for primary and secondary distribution with an auxiliary power supply of 24-230 Vdc/ac, 48-230 Vdc/ac, or 24-48 Vdc (depending on model).

    • 4 current channels and 6 voltage channels for capacitive and resistive low-power voltage sensors (LEA).
    • Metallic box with high electromagnetic compatibility level (EMC) and wide range of operating temperature.
    • Protection of decoupling, load shedding, and loss of main (islanding). Loss of Main (islanding) occurs when part of the public utility network loses connection with the rest of the system. If this situation is not detected, the generator could remain connected, causing a safety hazard within the network. Automatic reconnection of the generator to the network may occur, causing damage to the generator and the network. SIR-A relay detects this situation thanks to its voltage and frequency functions focused on the Rate of change of frequency (ROCOF) method.
    • Signalling/control the circuit breaker (52 function) and the recloser (79 function).
    • The front part of the SIRA is provided with a navigation keypad made of 7 keys (including the RESET key), 6 programmable hot keys that by default are configured: two (2) keys to open and close the CB, two (2) keys to block and unblock the recloser and two (2) keys to put the relay in local or remote mode with their associated three (3) configurable control LEDs. Besides, depending on the model:
      • Adaptation B: Eight (8) programmable alarm LEDs
      • Adaptation C: Thirteen (13) programmable alarm LEDs + 8 configurable keys with their associated configurable LED.
    • Arc Flash detection (AFD) with 4 AFD inputs and 4 high-speed outputs available depending on the model. This functionality, along with the possibility of having WIFI communication, allows the users to set and configure the relay through Fanox free software and to operate the relay without being present in the installation, prioritizing security.
    • In case a CB is manually closed, a switch on to an existing fault may occur. This fault condition is critical if the overcurrent protection function does not clear the fault until the adjusted time delay is finished. It is necessary, in those cases, to clear the fault quickly by means of SOTF function.
    • To allow the communication, relays are provided with a local micro-USB front port and with remote communication with different options (ports and protocols) on the rear side:
      • Rear Serial Port: IEC60870-5-103, Modbus RTU or DNP3.0 Serial (selectable by general settings).
        • Adaptation B: Rear RS485 port
        • Adaptation C: Rear RS485 or RS232 port (selectable by the user, both ports are not available simultaneously)
      • Rear RJ45 Port: Modbus TCP/IP, DNP3.0 TCP/IP, IEC60870-5-104 (selectable by general settings) + SNTP Protocol + Web Server.
      • Rear RJ45: IEC61850.
    • Wireless communication (WiFi) and synchronization through IRIG-B are optional, depending on the model.
    • Alarms panel is available.
    • The SIR-A is provided with (depending on the model):
      • 8 configurable inputs and 7 configurable outputs.
      • 24 configurable inputs and 7 configurable outputs.
      • 8 configurable inputs and 18 configurable outputs.
      • 16 configurable inputs and 11 configurable outputs.
      • 8 configurable inputs, 7 configurable outputs, 4 AFD inputs, and 4 High-Speed outputs.
    • SIR-A is fitted with the demand of power (Load Data Profiling) with the following characteristics:
      • Number of records: 2160.
      • Recording mode circular.
      • Sampling rate (interval): configurable through communications (1-60 min).
    • Alarms panel is available.
    • SIR-A is provided with non-volatile RAM memory in order to store up to 3072 events and disturbance fault recording (DFR), maintaining date & time thanks to its internal RTC (real Time Clock).
      • 5 records in data and COMTRADE format (300 cycles each record): 1 to 8 pre-fault cycles + 292 to 299 post-fault cycles.
      • 25 records in data and COMTRADE format (60 cycles each record): 1 to 8 pre-fault cycles + 52 to 59 post-fault cycles.
      • 50 records in data and COMTRADE format (30 cycles each record): 1 to 8 pre-fault cycles + 22 to 29 post-fault cycles.
      • 100 records in data and COMTRADE format (15 cycles each record): 1 to 8 pre-fault cycles + 7 to 14 post-fault cycles.)
    • Each oscillographic record contains 10 analogue channels and up to 96 configurable digital channels. The oscillography is downloaded by a communications port. The SICom communications program allows the oscillography record to be downloaded and saved in COMTRADE format (IEEE C37.111-1991)
    ANSI CODE PROTECTIONS
    50 Instantaneous phase overcurrent
    67/51 Inverse Time Directional* Phase Overcurrent
    50N Instantaneous calculated neutral overcurrent
    50G Instantaneous measured neutral overcurrent
    67N/51N Inverse Time Directional* Calculated Neutral Overcurrent
    67G/51G Inverse Time Directional* Measured Neutral Overcurrent
    67NI Directional isolated calculated neutral overcurrent
    67GI Directional isolated measured neutral overcurrent
    SOTF Switch On To Fault
    46 Phase balance current protection
    46BC Broken Conductor Detection
    49 Thermal overload
    49T External Trip
    37 Instantaneous phase undercurrent
    SHB Second Harmonic Blocking
    59 Instantaneous phase overvoltage (Bus bar)
    59N Instantaneous Calculated neutral overvoltage (Bus bar)
    59-L Instantaneous phase overvoltage (Line)
    59N-L Instantaneous Calculated neutral overvoltage (Line)
    47 Phase Balance voltage protection (Bus bar)
    47-L Phase Balance voltage protection (Line)
    27 Instantaneous Phase undervoltage (Bus bar)
    27-L Instantaneous phase undervoltage (Line)
    27V1 Instantaneous Positive sequence undervoltage (Bus bar)
    27V1-L Instantaneous Positive sequence  undervoltage (Line)
    32 Directional Overpower
    81O/U Under/Overfrequency
    81R Rate of change of Frequency (ROCOF)
    78 Out of Step (Vector Shift)
    CLP Cold Load pickup
    79 AC Reclosing device
    SCM Sequence Coordination Mode
    SZM Sectionalizer Mode
    52 Breaker wear monitoring
    25 Synchro Check
    HLT Hot Line Tag
    50BF Circuit Breaker Failure
    74TCS Trip Circuit Supervision
    60CTS Phase CT Supervision
    60VTS Phase LPVT Supervision
    86 Trip lockout
    68 Zone selection interlocking (ZSI)
    PGC Programmable logic control
    * ANSI 67, ANSI 67G, and ANSI 67N can be converted into ANSI 51, ANSI 51G, and ANSI 51N, respectively by setting the “Directionality” parameter to NO.
    ADDITIONAL FUNCTIONS
    CNT Counters
    RTC Real Time Clock
    ALRM Alarm panel
    PGC Programmable Logic Control
    HMI Human Machine Interface
    SER Sequential Event Recording
    DFR Disturbance Fault Recording
    LDP Load Data Profiling
    MET Metering
    STTG Settings Groups
    CMMD Commands

    Communication Software for all Fanox Relays Range

    The SICom PC software has been designed and programmed to gain access to all Fanox relays information, modify the settings and configuration, check states and measurements, and analyze and save events and fault reports using a graphic-friendly user interface.

    SICom software works with Windows® Windows 7, Windows 8, Windows 8.1, and Windows 10 operating systems.

    • General data reading: Complete model, Version, Serial number, etc.
    • States reading
    • Measurements reading
    • Reading and changing settings
    • Reading and changing the configuration
    • Reading and deleting events
    • Reading and deleting fault reports
    • Reading and deleting demand current (load data profiling)
    • Reading and saving oscillographic records in Comtrade format
    • Changing the user passwords
    • Saving and Loading Settings files
    • Saving and loading configuration files
    • Saving events and fault reports
    • Saving demand current (load data profiling)
    • Date-time synchronization
    • Configuring the communication parameters
    • Reading and changing counters
    • Commands for opening and closing the circuit breaker and blocking/unblocking the recloser
    • Configuration of the inputs
    • Configuration of the outputs
    • Configuration of the causes that start a Fault Report

    The update of the software does not require any user´s action; if the computer is connected to the Internet, SICom updates itself when it is started.
    It will allow you to prepare all the settings and relay configurations without having the relay connected to the PC (offline mode), reducing engineering and commissioning time.
    SICom program uses Modbus protocol, so only the ports with this protocol can be used to establish the communication.

    SIR-ASIR-C
    TypeFeeder Protection and Recloser ControlFeeder Protection and Recloser Control
    Auxiliary SupplyDepending on the model: 24-48 Vdc (±20%) 48-230 Vac/Vdc (48-220 Vdc (±20%) / 100-230 Vac (±15%)). 24-230 Vdc/ac 24-220 Vdc (±20%) / 100-230 Vac (±15%)).24-230 Vac/dc (24-220 Vdc (±20%) / 100-230 Vac (±15%)).
    Consumption24-48 Vdc and 48-230 Vac/dc < 10VA. 24-230 Vac/dc < 20VA.24-230Vac/dc < 20VA
    Current measurement3/4 standard CT3/4 standard CT
    LPCTn/an/a
    Voltage measurementVoltage sensorsVoltage sensors
    VT connection typen/an/a
    Load data profiling (LDP)2160 records2160 records
    5022
    SOFT11
    50G11
    50N11
    67/5144
    67G/51G22
    67N/51N22
    67GI11
    67NI11
    64REF11
    4611
    46BC11
    4911
    49T11
    3711
    AFD1 (4 AFD inputs + 4 high-speed outputs) (Optional)
    2722
    27V111
    27V1-L1 (Optional)1 (Optional)
    27-L1 (Optional)1 (Optional)
    5922
    59N22
    59N-L1 (Optional)1 (Optional)
    59-L1 (Optional)1 (Optional)
    4711
    47-L1 (Optional)1 (Optional)
    3244
    81U/O66
    81R22
    7811
    79√ Up to 4 attempts. √ Up to 4 attempts.
    HLT11
    251 (Optional)1 (Optional)
    74TCS11
    60CTS11
    60VTS11
    50BF11
    SHB11
    CLP11
    52
    86
    SCM
    SZM
    IRIG-BOptionalOptional
    WIFIOptionalOptional
    Counters
    Commands
    Sett. Group66
    Inputs8 / 16 / 24 / 8 + 4 AFD8 / 11
    Outputs7 / 11 / 18 / 7 + 4 HS-O7 / 5
    LEDs11 configurable11 configurable
    HMI20x4 LCD + 13 keys20x4 LCD + 13 keys
    Event30723072
    Fault Reportconfigurable up to 100configurable up to 100
    Oscillographyconfigurable up to 100configurable up to 100
    Local Port (frontal)Micro USBMicro USB
    Remote Port (rear)RS485 or EthernetRS485 or Ethernet
    Communications ProtocolsRS485 (Modbus RTU, IEC60870-5-103 or DNP 3.0 Serial). RS485 (Modbus RTU, IEC60870-5-103 or DNP 3.0 Serial) + RJ45 (Modbus TCP, DNP 3.0 TCP or IEC60870-5-104) + Web Server + SNTP Protocol + IRIG-B. RJ45 (IEC 61850) + RJ45 (Modbus TCP, DNP 3.0 TCP or IEC60870-5-104) + Web Server + SNTP Protocol + IRIG-B. WiFi + RS485 (Modbus RTU, IEC60870-5-103 or DNP 3.0 Serial) + RJ45 (Modbus TCP, DNP 3.0 TCP or IEC60870-5-104) + Web Server + SNTP Protocol + IRIG-B. WiFi + RJ45 (IEC 61850) + RJ45 (Modbus TCP, DNP 3.0 TCP or IEC60870-5-104) + Web Server + SNTP Protocol + IRIG-B.RS485 (Modbus RTU, IEC60870-5-103 or DNP 3.0 Serial). RS485 (Modbus RTU, IEC60870-5-103 or DNP 3.0 Serial) + RJ45 (Modbus TCP, IEC60870-5-104 and DNP 3.0 TCP) + Web Server + SNTP + IRIG-B.
    Dimensions198x187x153.15 (mm)Vertical assembly HxWxD: 198x107x145.01 (mm) Horizontal assembly HxWxD: 107x198x145.01 (mm)

    RELATED PRODUCTS

    SIR-C
    Overhead Control / RTU & Feeder Protection

    The Fanox SIR-C is the relay that offers the optimal solution for recloser control and line feeder protection for primary and secondary distribution, by means of current, voltage, and frequency functions.
    It is available with 24-230 Vdc/AC, 48-230 Vdc/AC, or 24-48 Vdc auxiliary power supply (depending on the model that best suits the needs of the installation).
    • 4 current channels and up to 6 voltage channels, with the advantage of measuring the voltage through capacitive or resistive sensors.
    • Very intuitive and easy to use
    • Allows communications; rear port (RS485 for serial and RJ45 for ethernet interface) and front port through a micro USB connector.
    • Multiple industrial protocols: DNP3.0 and Modbus RTU, IEC60870-5-103, IEC60870-5-104, IEC61850.
    • Clears fault quickly through the SOFT (Switch On To Fault) function.

    Ansi Code Functions
    50, 67/51, 50N, 50G, 67N/51N, 67G/51G, 67NI, 67GI, SOTF, 46, 46BC, 64REF, 49, 49T, 37, SHB, 59, 59N, 59-L, 59N-L, 47, 47-L, 27, 27-L, 27V1, 27V1-L, 32, 81O/U, 81R, 78, CLP, 79 AC, SCM, SZM, HLT, 52, 25, 50BF, 74TCS, 60CTS, 60VTS, 86, 68, PGC

    *ANSI 67, ANSI 67G, and ANSI 67N can be converted into ANSI 51, ANSI 51G, and ANSI 51N, respectively by setting the “Directionality” parameter to NO.

    Additional Functions
    CNT, RTC, ALRM, PGC, HMI, SER, DFR, LDP, MET, STTG, CMMD