Dual & Self powered OC&EF Protection Relays

The SIA-B is Dual & Self powered Overcurrent and Earth Fault Protection Relay, using the operating current through three specific current transformers fitted on the lines.

Data Sheet

    Get in touch with our Technical Support:

    Select your Country*

    Description

    This adaptation of the SIA-B relays offer reduced dimensions, making this relay easy to install, and its lightweight helps the customer to save costs in transport.

    The protection relay offers the advantage in self-powered mode, SIA-B starts up from 0.4 times the minimum primary current of the CT (three-phase current).

    SIA-B is suitable for RMUs, SF6 insulated, and compact switchgear in those installations where the space is critical, making the maintenance much more manageable.

    USB front port connection (ModBus RTU protocol) for local communication. Remote communication through rear RS485 (ModBus RTU)

    The relay is self-powered using the operating current through three specific current transformers fitted on the lines. These transformers are also used to obtain current measurements. Besides, SIA-B can be used with an auxiliary power supply (24-230Vac/dc). The relay can be also supplied by a USB cable connected to the laptop, with the USB KITCOM adapter or a standard power bank.

    The SIA-B, Self-powered Protection Relays fits perfectly in EATON Xiria SF6Free medium voltage switchgear and requires minimal inspection, and maintenance leading to low operation costs.

    Fanox SIA-B is a great addition to Xiria offering and creating more versatility for its growing customer base. This cooperation benefits the end-users. It can be used for more demanding applications; photovoltaic, windfarm, renewable energy.

    The SIA-B is an OC&EF protection relay with self-powered and dual-powered (self-powering + auxiliary power) options.
    • The relay is self-powered using the operating current through three specific current transformers fitted on the lines. These transformers are also used to obtain current measurements. Besides, SIA-B can be used with an auxiliary power supply (24-230Vac/dc). The relay can be also supplied by a USB cable connected to the laptop, with the USB KITCOM adapter or a standard power bank.
    • Internal commissioning battery included (Lithium battery: 20 years lifetime), as optional.
    • Metallic box with high electromagnetic compatibility level (EMC) and wide range of operating temperature.
    In self-powered mode, SIA-B starts-up from 0.4 times the minimum primary current of the CT (three-phase current).
    • Test menu allows the trip circuit to be tested before the transformation centre is powered up.
    • Bistable magnetic indicator (flag) which indicates the trip condition, maintaining its position even though the relay loses the supply.
    • Self-diagnosis of the relay status (WATCHDOG) through a LED.
    • Low power consumption.
    • To allow communication, relays are provided with a local micro USB front port and with optional remote communication RS485 port (Modbus RTU protocol) on the rear side.
    • The SIA-B is provided with a trip output for low power coil (24 Vdc – 135 mJ) and depending on the model, 1 external trip input and 2 configurable outputs.
    • The SIA-B is provided with non-volatile RAM memory in order to store up to 100 events and disturbance fault recording (DFR – 4 fault reports in data format), maintaining date & time thanks to its internal RTC (Real Time Clock) even without power supply.
    • The installation and subsequent maintenance of external batteries are eliminated. The operating costs of the centre are reduced.
    • Its compact size makes SIA-B easy to install and its lightweight helps the customer to save costs in transport.

    50 Instantaneous phase overcurrent

    51 Inverse time overcurrent

    51N Inverse time calculated neutral overcurrent

    49T External trip

    50N Instantaneous calcalated neutral overcurrent

    49 Thermal image

    49T External trip

    PGC Programmable logic control

    TB Trip Block for switch disconnector

    Communication Software for SIA & SIL protection relays

    The SICom PC software has been designed and programmed to gain access to all of Fanox relays information, to modify the settings and configuration, check states and measurements and to analyse and save events and fault reports using a graphic-friendly user interface.

    SICom software works with the Windows® Windows 7, Windows 8, Windows 8.1 and Windows 10 operating system.

    • General data reading: Complete model, Version, Serial number, etc.
    • States reading
    • Measurements reading
    • Reading and changing settings
    • Reading and changing configuration
    • Reading and deleting events
    • Reading and deleting fault reports
    • Reading and deleting demand current (load data profiling)
    • Reading and saving oscillographic records in Comtrade format
    • Changing the user passwords
    • Saving and Loading settings files
    • Saving and Loading configuration files
    • Saving events and fault reports
    • Saving demand current (load data profiling)
    • Date-time synchronization
    • Configuring the communication parameters
    • Reading and changing counters
    • Commands for opening and closing the circuit breaker and block/unblock the recloser
    • Configuration of the inputs
    • Configuration of the outputs
    • Configuration of the causes that start a Fault Report

    The update of the software does not require any user´s action, this is, if the computer is connected to Internet, SICom updates itself when it is started.
    It will allow you to prepare all the settings and relay configurations without having the relay connected to the PC (offline mode), reducing engineering and commissioning time.
    SICom program uses Modbus protocol, so only the ports with this protocol can be used to establish the communication.

    SIA-B Specific CT'sSIA-B Standard CT'sSIA-C Standard CT'sSIA-F
    TYPESELF & DUAL POWERED (SELF+AUX)SELF & DUAL POWERED (SELF+AUX)SELF & DUAL POWERED (SELF+AUX)AUXILIARY POWERED
    Auxiliary Supply24-230 Vac/dc24-230 Vac/dc24Vdc230Vac48 Vdc110-230 Vac/Vdc24-220 Vcc / 48-230 Vac
    Self Power SupplyI > 0,35 x Is min (x3)0,075 In (x3)0,1 In (x3)
    External batteryUSB cable / Power bankUSB cable / Power bankKITCOMUSB cable / Power bank
    Internal battery√ (*)√ (*)
    Consumption0,5 W1,5 W0,5 W1,5 – 2,2 W
    CTSpecific CTStandard CT/1A - 2VAStandard CT/1A - 2.5VA Standard CT/5A - 5VAStandard CT/1 - 0,5VA Standard CT/5A - 0.5VA
    501221
    50G221
    50N1
    511111
    51G111
    51N1
    SHB111
    74CT1
    46BC1
    4611
    791
    52111
    50BF111
    491111
    49T1111
    CLP111
    74TCS 1
    Trip Block111
    68 Zone Selection interbloking111
    86
    PGCProgrammable LogicV3V3V3V3
    Counters
    Commands
    Sett. Group243/43
    Inputs--- EXT.TRIP3 DI--- EXT.TRIP 2DI 2DI + EXT.TRIP--- 2DI
    Outputs--- 2NC-NO3 NC-NO--- 2 NC-NO 3 NO1 NO + 2 NC-NO
    Output for STRIKER24 Vdc – 135 mJ24 Vdc – 135 mJ24 Vdc – 135 mJ
    LEDs2 LEDs 2 LEDs +1MAG.FLAG4 LEDs3 LEDs + 1 MAG.FLAGS 3 LEDs + 3 MAG.FLAGS3 LEDs configurable
    HMI20x2 LCD + 7/8 keys20x2 LCD + 8 keys20x2 LCD + 7/8 keys20x2 LCD + 7 keys
    Event10010241024200
    Fault Report420204
    Oscillography10 records x 50 cycles10 records x 50 cycles1 record x 22 cycles
    Current demand
    Local Port (frontal)Micro USBMicro USBRS232 Micro USBMicro USB
    Remote Port (rear)RS485RS485RS485RS485
    Communications ProtocolsModBus RTUModBus RTU ModBus RTU or DNP3.0ModBus RTU ModBus RTU or IEC60870-5-103ModBus RTU DNP3.0
    Size of (HxW)Vertical: 120,65 x 167,80 mmHorizontal: 185,80 x 102,7 mm90 x 245 mmVertical Compact: 177 x 155 mmVertical Standard: 177 x 189 mmHorizontal: 177,8 x 290,3 mm167,80 x 120,65 mm

    Related Products

    Advanced OC&EF Self-Powered Relay

    SIA-B is the most reliable dual powered (Self-Powered + Universal Vaux) relay offering a high performance previously available only in relays with Vaux:

    Remote communications for SCADA (Modbus or DNP3.0 protocols)

    • Up to 10 COMTRADE records
    • Advanced protection functions
    • Completely configurable I/O thanks to advanced logic

    Ultra-fast SOTF
    Very low start-up levels and minimum consumption <2 VA
    Compact design

    Ansi Code Functions

    50, 51, 50G, 51G, 49, 46, SHB, 49T, TB, 52, 50BF, CLP, 68, PGC

    SIA-C
    Dual & Self-Powered OC&EF Protection Relays

    Counting with an extensive experience of successfully operating devices in the field worldwide and thanks to these unique advantages, SIA-C enjoys top recognition among users all around the planet.

    Above all, the different mechanics available by model list make our SIA-C the best choice for our customers, covering all the needs of the market

    Remote communications RS485 Modbus RTU or IEC 60870-5-103

    • Self-Powered & Dual-Powered (Self+Vaux)
    • Standard CTs /1 or /5
    • Low start-up levels
    • Load data profiling
    • Self diagnosis (watchdog)
    • Non-volatile RAM memory (up to 1.024 events and 20 fault report), maintaining date & time even in SP mode, thanks to its internal RTC
    • With internal commissioning battery as optional
    • Withdrawable model as optional

    Ansi Code Functions

    50, 51, 49T, 51G, 50G, 46, 46BC, 49, SHB, CLP, 79, 52, 50BF, 74TCS, 60CTS, 68, PGC

    TESTING BLOCKS & PLUGS FTB/FTP

    Advantages

    FANOX FTB/FTP test block allows testing the protection, control, metering and/or communication device of a facility connected to field switchgear, easily and safely, isolating the circuits fully and eliminating all risks for the user.

    • Maximum safety for the user.
    • Internal automatic CT short circuiting.
    • Single hand fully isolated plug.
    • Locking system for safest operation.
    • Possibility of horizontal or vertical mounting, respectively.